Milić Cables

Bare Conductors

Bare conductors are electrical conductors without insulation, usually made of copper or aluminum. They are used in power systems for the transmission and distribution of electricity, mainly in transmission lines. Due to the absence of insulation, they are suitable for outdoor use, where there is sufficient distance between the conductors and other objects to avoid the danger of a short circuit. Their main advantage is economy and simple maintenance, while their use is limited to situations where safety standards are met.

BARE CONDUCTORS

Al ropes for overhead lines (SRPS N.C1.302)

Construction: Al rope is a construction of seven or more aluminum wires (hard-drawn) according to SRPS N.C1.301 used in concentric layers. Adjacent layers have opposite directions of use, with the outer layer having a right-hand direction.

Image
Nominal cross-section
Calculation section
Construction al
Rope diameter
Net weight (approximate)
Breaking strength
mm²
mm²
n x d
mm
kg/km
kN
16
15.89
7 x 1,79
5.1
44
2,90
25
24.25
7 x 2,10
6.3
67
4,25
35
34.36
7 x 2,50
7.5
94
5,85
50
49.48
7 x 3,00
9.0
135
8,10
50
48.35
19 x 1,80
9.0
133
8,60
70
65.81
19 x 2,10
10.5
181
11,50
95
93.27
19 x 2,50
12.5
256
15,95
120
116.99
19 x 2,80
14.0
322
19,10
BARE CONDUCTORS

Al/Če ropes for overhead lines (SRPS EN 50182, SRPS N.C1.351)

Construction: Al/Fe rope is a construction of seven or more wires wound in concentric layers. The rope core consists of one or more galvanized steel wires wound in concentric layers.

Image
Area
Construction
Rope diameter (mm)
Weight
Design breaking force (kN)
Maximum resistance at 20°C (Ohm/km)
Nominal cross-section
Calculation section
Construction Al
Number of layers
Construction Če
Weight Al (kg/km)
Weight Če (kg/km)
Net (kg/km)
Al/Če ropes (mm²)
Section ratio (Al/Če)
Al (mm²)
Če (mm²)
Total (mm²)
16/2,5
6
15,3
2,5
17,8
6 x 1,80
1
1 x 1,80
5,4
41,8
19,9
61,6
5,80
1,8769
25/4
6
23,9
3,9
27,8
6 x 2,25
1
1 x 2,25
6,8
65,4
31,0
96,3
8,35
1,2012
35/6
6
34,4
5,7
40,1
6 x 2,70
1
1 x 2,70
8,1
94,2
44,7
138,7
12,37
0,8342
50/8
6
48,3
8,0
56,3
6 x 3,20
1
1 x 3,20
9,6
132,2
62,7
194,8
16,81
0,5939
70/12
6
69,9
11,4
81,3
26 x 1,85
2
7 x 1,44
11,7
194
90
282,2
26,27
0,4132
95/15
6
94,4
15,3
109,7
26 x 2,15
2
7 x 1,67
13,6
263
121
380,6
34,93
0,3060
150/25
6
148,9
24,2
173,1
26 x 2,70
2
7 x 2,10
17,1
402
189
600,8
53,67
0,1940
240/40
6
243,1
39,5
282,5
26 x 3,45
2
7 x 2,68
21,8
657
307,3
980,1
82,12
0,1188
360/57
6
360,2
56,3
416,5
26 x 4,20
2
7 x 3,20
26,4
973,6
438
1442
121,76
0,08014
490/65
7,7
490,3
63,6
553,9
54 x 3,40
3
7 x 3,40
30,6
1325,3
495
1852,9
150,81
0,0590
BARE CONDUCTORS

Galvanized steel ropes for overhead lines (SRPS N.C1.702)

Construction: Steel rope is a construction of seven or more steel wires according to SRPS N.C1.701 used in concentric layers. Adjacent layers have opposite directions of use, with the outer layer having a right-hand direction. It is used as lightning protection.

Image
Nominal cross-section
Calculation section
Construction če
Rope diameter
Net weight (approximate)
Breaking strength
mm²
mm²
n x d
mm
kg/km
kN
16
15.89
7 x 1,70
5.1
126
18,75
25
24.25
7 x 2,10
6.3
192
30,80
35
34.36
7 x 2,50
7.5
272
43,75
50
49.48
7 x 3,00
9.0
391
63,00
50
48.35
19 x 1,80
9.0
384
61,55
70
65.81
19 x 2,10
10.5
523
83,80
95
93.27
19 x 2,50
12.5
741
118,75
120
116.99
19 x 2,80
14.0
929
148,95
BARE CONDUCTORS

Cu ropes for overhead lines (DIN 48 201 Teil 1)

Construction: Cu rope is a construction of seven or more copper wires (soft-drawn or hard-drawn) according to DIN48 200 taught in concentric layers.

Image
Nominal cross-section
Calculation section
Construction Cu
Rope diameter
Net weight (approximate)
Breaking strength
mm²
mm²
n x d
mm
kg/km
kN
10
10,02
7 x 1,35
4.1
90
4,02
16
15,89
7 x 1,70
5,1
143
6,37
25
24,25
7 x 2,10
6,3
218
9,72
35
34,36
7 x 2,50
7,5
310
13,77
50
49,48
7 x 3,00
9,0
446
19,84
50
48,35
19 x 1,80
9,0
437
19,38
70
65,81
19 x 2,10
10,5
596
26,38
95
93,27
19 x 2,50
12,5
845
37,39
120
147,11
37 x 2,25
15,8
1337
58,98
150
147,11
37 x 2,25
15,8
1337
58,98
185
181,62
37 x 2,50
17,5
1649
72,81
240
242,54
61 x 2,25
20,3
2209
97,23
300
299,43
61 x 2,50
22,5
2725
120,04